Appendix A - Specifications
Characteristic
PVP250kW
(600VAC)
PVP250kW
(480VAC)
PVP260kW
(480VAC)
PVP260kW-LV
(480VAC)
AC Characteristics
Continuous power (AC) 249.5kW 260kW
Grid type
3 phase, 4 wire Y
(not compatible with delta service)
Nominal AC voltages (VAC) 600 Y 480 Y
Maximum output fault current and duration
(Also called maximum fault current contribution)
1200A/29 ms
Maximum utility backfeed current (A) 593
AC maximum continuous current (A) 243 304 316
CEC efciency (%) 96.5 96.5 97 96.5
Peak efciency (%) 97.7
Frequency range 59.3 - 60.5Hz
AC voltage range set points (default) (-12% to +10%)
AC operating range (V)
528VAC –
660VAC
423VAC – 528VAC
Power factor at full power > .99
THD (%) < 3%
Standby losses (W) 90 67
Utility interconnect voltage trip limits and times See Appendix D
Utility frequency trip limits and times See Appendix D
DC Characteristics
DC input busbar rating 1,600 A
Maximum operating input current (A) 890 925 1,030
Subcombiner DC fuse options
(
1600A max. total fusing)
75A - 400A
MPPT range 295-595 265-595
Maximum V
oc
600
Startup voltage VDC 330 300
General Specications
Cooling Forced Convection
Operating ambient temperature range (°C) -30 to 50°
Standby/storage ambient temperature range (°C) -40 to 60°
APPENDIX A