PV Powered PVP260kW Technical Information Page 108

  • Download
  • Add to my manuals
  • Print
  • Page
    / 129
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 107
93
Appendix D - Limits, Fault Codes, Torque
Values, and Wire Sizes
Condition
Factory setting
(VAC or Hz)
Range (VAC)
Maximum
Trip Time(s)
480VAC Conguration
Voltage phase high 304.8 304.8 – 332.5 1.0
Voltage phase low 243.9 216.1 – 243.9 2.0
Voltage phase fast high 332.5 332.5 0.16
Voltage phase fast low 138.6 138.6 0.16
600VAC Conguration
Voltage phase high
381.1 381.1 – 415.7 1.0
Voltage phase low
304.8 270.2 – 314.8 2.0
Voltage phase fast high
415.7 415.7 0.16
Voltage phase fast low
173.2 173.2 0.16
All Congurations
Line frequency low 59.3 Hz 57.5-59.8 0.16
Line frequency high 60.5 Hz 60.5 0.16
Table D-1 Voltage and Frequency Limits
Condition Adjustable Setting (VAC) or (Hz)
AC Voltage Field Adjustable Trip Points (% of Nominal) -22% to +20%
Accessible Range of Low Frequency Setting (Hz)
(Limits of Accuracy Frequency Measurement +/-0.1
Hz)
Adjustable low trip 57.5-59.8
High trip xed at 60.5
Accessible range of Trip Times
(Limits of Accuracy Time Measurement +/- 0.1 sec.)
.16 to 300 seconds
Table D-2 Adjustable Voltage and Frequency Limits
APPENDIX D