PV Powered PVP260kW Technical Information Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 129
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
22
Front – A front clearance of three (3) feet is required to open and maintain the unit per
NEC 110.26 or applicable Canadian Electrical Code.
Top – A top clearance of 18 inches above the air intake hood is required to maintain the
lters and blowers.
Clearances are shown in the gure below.
1. Only one side, right or left, is recommended to have the full 36”clearance while the remaining side must
have 12”. The above example demonstrates 12” on the left with 36” on the right side. This allows access
to the magnetics section for retorquing bolts and thermal scan of connections. This is not an NEC setback
requirement and 12” on each side is an acceptable installation practice.
Figure 3-1 Inverter Clearances
3.4 Conduits and Conductors
All the external conduits and conductors are to be supplied by the installer. See
Appendix
C - Mechanical Drawings
for inverter gland plate locations. The gland plates must be in
place for operation of the inverter.
All interconnect wiring and power conductors interfacing to the inverter must be in
accordance with the NEC and ANSI/NFPA 70 or applicable state or local standards.
Installations in Canada should be in accordance with the Canadian Electrical Code or
applicable provincial or local standards.
Large gauge wire must conform to the minimum bend radius specied in the NEC,
Article 373-6B, Ninth Edition and all applicable local codes.
All conductors shall be rated for 90
o
C (minimum).
External Cable Interfaces: Entry through bottom or side gland plates. See
Appendix C -
Mechanical Drawings
for details.
18 inches
3 feet
2 inches Clearance
Required Behind
Unit
12 or 36
inches
12 or 36
inches
Page view 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 128 129

Comments to this Manuals

No comments