70
6.5 Shutdown Procedure
To shutdown the inverter, complete the following steps in order:
1. Turn the inverter’s ON/OFF switch to the OFF position.
2. Turn the AC disconnect to the power OFF position by rotating the AC power lever
to the position shown in Figure 2-1. The display on the upper front panel should be
inactive.
3. Turn the DC disconnect to the power OFF position by rotating the DC power lever to
the OFF position shown in Figure 6-10.
4. Open the utility connection circuit breaker.
5. Disconnect the PV array connection to the inverter using the external PV disconnect.
DC Disconnect
in Power OFF
Position
AC Disconnect
in Power OFF
Position
ON/OFF Switch
in OFF Position
Figure 6-10 AC and DC Disconnect Power OFF
!
DANGER
Risk of Electrical Shock. Allow ve (5) minutes for internal power to
dissipate prior to entering the enclosure cabinet. Ensure all terminals are
voltage free with the use of a multimeter.
!
DANGER
Risque d’électrocution. Laissez passer cinq (5) minutes an de permettre la
dissipation du courant interne avant d’ouvrir les panneaux du dispositif. Utilisez
un multimètre sur toutes les bornes an de conrmer l’absence de courant.
Comments to this Manuals