Figure 4‑12. DC side entry gland plates
2. Remove the gland plate while taking care not to damage the weatherproof
gasket material on the back side of the plate.
3. Punch holes as needed in the gland plate.
4. Attach watertight NEMA 4 conduit hubs in each hole.
The inverter is a NEMA 4 enclosure. Use only rain-tight or wet-location
conduit hubs and install these hubs as shown in the following figure.
4348
Lower cabinet
gland
plate
2 inch straight metal
conduit
connector
Figure 4‑13. Installation of conduit hub
CAUTION:
For outdoor installations make liquid-tight connections to the unit.
ATTENTION:
Pour les installations extérieures, effectuer des connexions étanches
à l’unité.
5. Replace the gland plate taking care to evenly seat the gasket material against
the cabinet.
Advanced Energy® PVP250kW and PVP260kW Inverters
570-1001792-05A Installing 4‑11