Page view 27
Magnetics compartment contains the isolation transformer and inductors
Power Module Assembly
The inverter uses insulated gate bipolar transistors (IGBTs) for converting DC power
into three-phase AC power. The inverter is protected by over-current, over-voltage,
and over-temperature detection controls. If a protection system is activated, the
power module will cease power conversion and send an interrupt signal to the digital
signal processor (DSP).
Card cage assembly
Figure 2‑2. Power module assembly
Card Cage Assembly
The card cage assembly in the following figure is designed to enable fast and easy
service and also acts as an EMI shield to ensure signal integrity on the following
PCBs:
Communications PCB: Provides serial, internet, and Modbus communications.
Power distribution PCB: Distributes the required logic level voltages for use
throughout the inverter.
Controller PCB: Controls sine wave generation, logic functions, and protection
activities. All analog and digital inputs and outputs are routed to the control
PCB.
I/O PCB: Provides a central location for a range of input, output, and control
circuits.
Advanced Energy
2‑4 Product Overview 570-1001792-05A