Modbus Data Registers
Table 6‑18. Modbus data registers
Description Start
Register
End
Register
No. of
Registers
Modbus
Address
Data
Type
Notes
Modbus base address = 1000
VoltsA L-N 1000 1001 2 41001 FLOAT ± 32 bit IEEE 754
VoltsB L-N 1002 1003 2 41003 FLOAT ± 32 bit IEEE 754
VoltsC L-N 1004 1005 2 41005 FLOAT ± 32 bit IEEE 754
Current A 1006 1007 2 41007 FLOAT ± 32 bit IEEE 754
Current B 1008 1009 2 41009 FLOAT ± 32 bit IEEE 754
Current C 1010 1011 2 41011 FLOAT ± 32 bit IEEE 754
DC input
voltage
1012 1013 2 41013 FLOAT ± 32 bit IEEE 754
DC input
current (see
note)
1014 1015 2 41015 FLOAT ± 32 bit IEEE 754
Line
frequency
1016 1017 2 41017 FLOAT ± 32 bit IEEE 754
Line kW 1018 1019 2 41019 FLOAT ± 32 bit IEEE 754
Total kWh
delivered
1020 1021 2 41021 UDINT 0 to 4.29e9
PV input
voltage
1022 1023 2 41023 FLOAT ± 32 bit IEEE 754
DC kW
(calculated)
1024 1025 2 41025 FLOAT ± 32 bit IEEE 754
Time since
epoch
1026 1027 2 41027 FLOAT Seconds since
01/01/1970
Total kWh 1028 1029 2 41029 UDINT ± 32 bit IEEE 754
Modbus Status and Fault Code Registers
The following table provides information about the registers that are used to report
status and fault codes. Each of these registers provides information about a group of
status codes or faults. For more information on the specific faults that can be reported
for each of the fault registers, see the troubleshooting information for the inverter.
For more information about the status codes, see Table 620 on page 627 and
Table 621 on page 627.
Advanced Energy® PVP250kW and PVP260kW Inverters
570-1001792-05A Data Monitoring and Controls 6‑25