PV Powered LLC 8 32-29-28-20-306
2.3.a Grounding
A single point ground connection is located in the lower right hand side of the
StarInverter cabinet. The PV panel grounding wire is terminated there. The AC
ground connection is terminated next to the Line and Line 2/Neutral connections
on the circuit board. The PV ground is bolted to the cabinet with a ¼-20 bolt.
(Refer to Figure 7.)
Figure 6 includes schematic representations of the PVP3200, PVP2900 , PVP2800-
XV and PVP2000 single point grounding. The front cover is grounded through the
two cover mounting screws.
Line
Filter
Control pcb
Power Distribution PCB
DC
Power
Supply
L1
L2
GND
PV GND
20 A SB
System Block Diagram
120/240 VAC
60Hz
PV
DC input
PVP3200,PVP2900,
PVP2800-XV & PVP2000
+
GND
1A
GF Detect Circuit
-
Figure 6: System Block Diagram showing single point ground point